| Total current distortion not
higher than 5% at rated load. Corresponding to the harmonic
restraint guidelines. Since the high power factor is 99% or
higher (at rated load), the power capacity can be greatly reduced.
Since 100% continuous regeneration is possible, the braking
capability of the AC drive is greatly improved. |

| Performance/function |
200V series |
400V series |
| Supply voltage |
Three-phase three-wire
200`230V 50/60Hz |
Three-phase three-wire
380`460V 50/60Hz |
| Output voltage |
320`358V |
640`716V |
| Applicable inverter capacity (kW) |
15, 22, 30, 37, 45, 55, 75, 90, 150, 180 |
11, 15, 22, 30, 37, 45, 55, 75, 110, 160, 200, 250, 315, 400, 500, 750, 1000 |
| Harmonic content (current) |
5% or less (at 100% load) |
| Input power factor |
99% or higher (at 100% load),
95% or higher (at load of 30% or more) |
| Overload capacity |
Operating state of rated current
150% continuously for 1 minute |
| Protective structure (JEM1030) |
IP00 (open type) |
| Protective function |
DC overvoltage, instantaneous
overcurrent, overload, overheating, power element abnormality,
AC/DC fuse blown |
| Input signal |
Operation/fault reset/external
fault |
| Output signal |
Operation/fault reset/inverter
operation permission (Ic relay contact)/multi-function analog
meter output |
| Ambient conditions |
Ambient temperature 0 to 50°C
Humidity 90%RH or lower (no dewing condensation)
Storage temperature -20 to 60°C (temperature range applicable
in a short time during transportation, etc.) |
|
|